Technical Information | ||
OUTDOOR MODEL | CRV240T | |
INDOOR MODEL | EVV240S | |
1 Total (Gross) Capacity (kW) (AS/NZS3823.1.2) | Cooling (Rated) | 21.55 |
Heating (Rated) | 22.50 | |
Nett (Rated) Capacity (kW) (AS/NZS3823.1.2) | Cooling (Min/Rated/ ) | 5.20 / 21.00 / 24.00 |
Heating (Min/Rated/ ) | 5.00 / 23.00 / 25.00 | |
Input Power (kW) (AS/NZS3823.1.2) | Cooling (Rated) | 6.10 |
Heating (Rated) | 6.57 | |
2 EER Rated (AS/NZS3823.1.2)
3 COP Rated (AS/NZS3823.1.2) |
Cooling (Rated) | 3.44 |
Heating (Rated) | 3.50 | |
Power Supply (V / Ph / Hz) |
Outdoor | 400V / 3Ph + N / 50Hz |
Indoor | 230V / 1Ph + N / 50Hz | |
Rated Load Amps (AS/NZS3823.1.2) Full Load Amps (AS/NZS3823.1.2) | Outdoor / Indoor / Total | 8.4 / 3.8 / 12.2 |
Outdoor / Indoor / Total | 16.6 / 6.0 / 22.6 | |
4 Circuit Breaker Amps | 25.0 | |
IP Rating |
Outdoor | IP44 |
Indoor | IP20 | |
Compressor |
Type / No. per Unit | Tru-Inverter Variable Speed Scroll / 1 |
Starting Method | Inbuilt Soft Starting | |
No. Refrigeration Circuits/No. Capacity Stages (Capacity range) | 1 / Variable Capacity (20-100%) | |
Refrigerant | R410A | |
Fans (Type x Number per unit) |
Outdoor | Axial / 6 Pole External Rotor / Direct Drive x 2 |
Indoor | Twin Deck Centrifugal / ECM Direct Drive x 1 | |
Airflow Range Indoor (l/s) |
Maximum | 1360 |
Nominal | 1130 | |
Minimum | 960 | |
Outdoor Dimensions (mm) |
Depth | 685 |
Height | 1105 | |
Width | 1685 | |
Indoor Dimensions (mm) |
Depth | 695 |
Height | 485 | |
Width | 1470 | |
5 Nominal Weight (kgs) |
Outdoor | 209 |
Indoor | 78 | |
6 Sound Pressure Level (dBA)
7 Sound Power Level (dBA) |
Outdoor (low/high fan) | 44.3 / 46.9 / 60.0 |
Outdoor (low/high fan) | 63.7 / 65.8 /79.6 | |
MEPS Compliant | Yes | |
8 Demand Response Capability (AS4755.3) | Capable |
ActronAir Advance CRV240T | EAA240S 21kW Split Ducted System | 3 Phase
ActronAir Advance CRV240T / EAA240S 21kW Split Ducted Systems – Three Phase | Splittable Indoor
Includes 7 day wall controller – 8 Zone
Optional available Supply Air Vbox:
What’s an Inverter, and what’s a Tru-Inverter?
Unlike conventional inverter compressors, which use ‘step, rest and stop’ cycles that cause the temperatures to jump up and down each step, the Tru-Inverter is vastly more precise, getting to the desired temperature faster, smoother, and maintaining it to within +/- 0.3°C at the sensor location – that means more comfort and a more comfortable electricity bill.
Why choose a Tru-Inverter?
Tru-Inverter can operate down to 20% of capacity for improved efficiency, as opposed to conventional inverters which can only operate down to 40% of capacity. Not only that, it can also heat and cool your home a phenomenal 5 times faster than conventional inverter systems.
To view the Brochure
Click here
Description
21.0 kW Cooling
23.0 kW Heating
Tru-Inverter | 2 Piece Indoor