Model Name
|
Indoor unit
|
FCTA125AVMA | ||
FCA125CVMA | ||||
Outdoor unit | RZAV125F2Y1 | |||
Power supply | 3 Phase, 380-415V, 50Hz | |||
Cooling capacity 1,3 Rated (Min. – Max.) |
kW | 12.5 (3.5-15.0) |
||
Heating capacity 2,3 Rated (Min. – Max.) |
kW | 15.0 (3.5-17.5) |
||
Power consumption
|
Cooling 1 | kW | 3.25 | |
Heating 2 | kW | 3.41 | ||
EER | Cooling | kW/kW | 3.85 | |
COP | Heating | kW/kW | 4.4 | |
AEER | Cooling | 3.79 | ||
ACOP | Heating | 4.34 | ||
TCSPF (Cooling) Commercial / Residential
|
Hot | 7.02 / 6.09 | ||
Average | 7.39 / 5.44 | |||
Cold | 8.45 / 5.66 | |||
HSPF (Heating) Commercial / Residential
|
Hot | 5.64 / 5.64 | ||
Average | 5.23 / 4.93 | |||
Cold | 4.71 / 4.33 | |||
Indoor unit
|
Colour
|
Unit | ——— | |
Decoration panel | Fresh White | |||
Airflow rate (H / HM / M / ML / L)
|
/s | 608 / 558 / 500 / 442 / 383 | ||
m3/min |
36.5 / 33.5 / 30.0 / 26.5 / 23.0
|
|||
Sound pressure level4 (H / HM / M / ML / L) | dB(A) |
46.0 / 43.5 / 41.0 / 38.5 / 36.0
|
||
Dimensions (HXWXD)
|
Unit | mm | 298X840X840 | |
Decoration panel | mm | 50X950X950 | ||
Machine weight
|
Unit | kg | 26 | |
Decoration panel | kg | 5.5 | ||
Certified operation range
|
Cooling | °CWB | 14 to 25 | |
Heating | °CDB | 15 to 27 | ||
Outdoor | Colour | Ivory White | ||
unit
|
Compressor
|
Type |
Hermetically sealed swing type
|
|
Motor output | kW | 3.3 | ||
Refrigerant charge (R-32) | kg | 3.70 (Charged for 40 m) |
||
Sound pressure level 4
|
Cooling / Heating | dB(A) | 50 / 51 | |
Night quiet mode | dB(A) | 46 | ||
Sound power level | dB(A) | ———– | ||
Dimensions (HXWXD) | mm | 870X1,100X460 | ||
Machine weight | kg | 95 | ||
Certified operation range
|
Cooling | °CDB | -5 to 50 | |
Heating | °CWB | -15 to 15.5 | ||
Piping connections
|
Liquid (Flare) | mm | o/ 9.5 | |
Gas (Flare) | mm | o/ 15.9 | ||
Drain
|
Indoor unit | mm | VP25 (I.D. o/ 25XO.D. o/ 32) | |
Outdoor unit 5 | mm | Connectable hose I.D. o/ 25 | ||
Max. interunit piping length | m | 85 (Equivalent length 100) | ||
Max. installation height difference | m | 30 | ||
Heat insulation | Both liquid and gas piping |
Daikin FCTA125A-VF2Y 12.5kW Premium Streamer Reverse Cycle Cassette Air Conditioner System | 3 Phase
12.5 kW Cooling
15.0 kW Heating
Daikin FCTA125A-VF2Y 12.5kW Premium Streamer Cassette Reverse Cycle – 3 Phase
Includes Indoor – FCTA125AVMA | Outdoor – RZAV125F2Y1 | 1 Phase
Fascia – BYCQ125EAF
Wired Controller – BRC1H63W
Key Features
Round Flow Cassette with Streamer
- Available in – Reverse Cycle (Heating & Cooling)
- Capacities – Premium Inverter: 5.0kW-14.0kW
- Refrigerant- R32
Energy Saving
- Energy consumption monitoring – Past power consumption is displayed for the current and previous days as well as in weekly and yearly intervals.
- Sensing sensor stop mode – When the room is unoccupied, the system stops automatically.
- Sensing sensor low mode – When the room is unoccupied, the set temperature is shifted automatically.
- Auto display OFF – While operation is stopping, the LCD display can be turned off. It can be displayed again when any button is pressed.
- Setpoint auto reset – Even if the set temperature is changed, the new set temperature returns to the previous preset value after a preset duration of time.
Comfort
- Circulation airflow – At the start of operation, airflow changes repeatedly between horizontal flow and downward flow (swing during cool operation), and air is sent throughout the room to eliminate uneven temperatures.
- Setbac – Maintains the room temperature in a specific range during unoccupied periods by temporarily starting an air conditioner that had been turned OFF.
- Quick start – At operation start, capacity priority operation is possible.
- Individual airflow control – Airflow direction can be individually adjusted for each air discharge outlet to deliver optimal air distribution.
- Infrared presence sensor – The sensor detects the presence of people in each of the 4 areas.
- Infrared floor sensor – The sensor detects the floor temperature and automatically adjusts operation of the indoor unit to reduce the temperature difference between the ceiling and the floor.
Cleanliness
- Streamer filter clean unit – Irradiates Streamer when the fan and air conditioning operation are stopped.
Streamer fumigates the cabin and sterilizes the filter. - Anti-bacterial air filter – The air filter has an anti-bacterial treatment to help prevent the growth of bacteria and mould on it.
Options
- High-efficiency filter – Two types are available: 65% and 90% colorimetry.
- Ultra long-life filter – Requires no maintenance for about 4 years* (10,000h) in stores and offices.
*For dust concentration of 0.15 mg/m3 - High performance prefilter (MERV 8 filter) – This filter can catch fine particles that cannot be removed by the existing prefilter, capturing 97% of 1.0-3.0 μm particles and 99% of 3.0-10 μm particles when air passes through the filter 10 times.
Description
12.5 kW Cooling
15.0 kW Heating
15.0 kW Heating
R32 | Includes BRC1H63W Controller