HITACHI PCI-6.5UFA1NQ / PAS-6.5UFASMQ1 16.0kW R32 airCore700 4-WAY Cassette split system – 3 Phase

SKU: PCI-6.5UFA1NQ / PAS-6.5UFASMQ1 / PHKF160PAQ1

PCI-6.5UFA1NQ – 16.0kW R32 airCore700 Multi Flow Cassette Indoor Unit
PAS-6.5UFASMQ1 – 16.0kW R32 airCore700 3Ø Inverter Outdoor Unit – Heat Pump
Fascia: PHKF160PAQ1 – Fascia to suit PCI-UFA1NQ
ALL AIRCORE 700 CASSETTE SPLIT SYSTEMS INCLUDE: PC-ARFG2-Z WIRED CONTROLLER

 

 



Model: Indoor / Outdoor Unit PCI-6.5UFA1NQ / PAS-6.5UFASMQ1
Power supply (Indoor) V/Ph/Hz 220~240V / 1Ø / 50Hz
Power supply (Outdoor) V/Ph/Hz 380~415V / 3Ø / 50Hz
Max. power input – Kw 6.27
Max. current input – A 12.0
Cooling Rated Capacity Kw

Cooling Capacity Range[Min~Max] kW

16.0

6.0~18.0

Heating Rated Capacity Kw

Heating Capacity Range[Min~Max] kW

18.0

6.5~20.0

Power comsumption – Cooling kW

Power Heating – Cooling kW

5.03

5.00

AEER Cooling

ACOP Heating

3.14

3.55

TCSPF(Cooling) Commercial / Residential – Hot

TCSPF(Cooling) Commercial / Residential – Average

TCSPF(Cooling) Commercial / Residential – Cold

5.34/4.89

5.46/4.40

5.91/4.62

HSPF(Heating) Commercial / Residential – Hot

HSPF(Heating) Commercial / Residential – Average

HSPF(Heating) Commercial / Residential – Cold

5.56/5.53

4.97/4.54

4.11/3.78

 

Indoor Unit – Fan Motor Output W

Indoor Unit – Air Flow[Hi2/Hi1/Hi/Med/Lo/SLo] L/S

Indoor Unit -Sound Pressure Level [Hi2/Hi1/Hi/Med/Lo/SLo] dB[A]

Indoor Unit – Sound Power Level dB[A]

Indoor Unit – Dimension [W×H×D] mm

Indoor Unit – Packing [W×H×D] mm

Indoor Unit – Net/Gross Weight kg

Indoor Unit – Drainage water pipe diameter mm

 

127

610/550/510/450

50/48/46/43

63

840×288×840

945×342×945

27/31

VP25

 

Outdoor Unit – Compressor Type

Outdoor Unit – Compressor R.L.A

Outdoor Unit – Fan Motor F.L.A

Outdoor Unit – Fan Motor Output W

Outdoor Unit – Air Flow m3/h

Outdoor Unit – Sound Pressure Level-Cooling dB[A]

Outdoor Unit – Sound Pressure Level-Heating dB[A]

Outdoor Unit – Sound Pressure Level-Night dB[A]

Outdoor Unit – Sound Power Level dB[A]

Outdoor Unit – Throttle Type

Outdoor Unit – Dimension [W×H×D] mm

Outdoor Unit – Packing [W×H×D] mm

Outdoor Unit – Net/Gross Weigh kg

 

ATH356SKRC9EQ

11.5

0.62

138

8200

57

59

54

74

Electronic Expansion Value

950×1380×320

1070×1520×470

108.0/118.5

Refrigerant type/Quantity Type

Refrigerant type/Quantity Charge Kg

Refrigerant type/Quantity GWP

R32

3.4

675

Design pressure H/L – MPa 4.15/2.21
Refrigerant pipe – Liquid side/Gas side MM

Refrigerant pipe – Max. pipe length M

Refrigerant pipe – Max. Height difference M

Refrigerant pipe – Add Refrigerant Amount g/m

Refrigerant pipe – Chargeless m

Φ9.52/Φ15.88

75

30

35

30

Guaranteed Temperature Operation Range – Cooling °C -5~52
Guaranteed Temperature Operation Range – Heating °C -20~15.5

 

airCore700 Cassette

 

Light Commercial Cassette Split AC System

The airCore700 stands as Hitachi’s flagship light commercial split system range. It delivers outstanding cooling and heating performance, showcasing a wide capacity range and efficient operation in diverse ambient temperatures, while guaranteeing uncompromised comfort. Utilising R32 refrigerant, airCore700 units have a lower global warming potential compared to R410A refrigerant products.

Peace of Mind with a 6 Year Warranty

The airCore700 ducted split range comes with a comprehensive 6 Year Warranty on parts and labour, so you can be assured of the reliability and quality of your airCore700 system.

Extreme Temperature Operation

Designed for the harshest conditions, Hitachi airCore700 units are designed to operate in ambient temperatures from -20°C to 52°C to ensure you’re always comfortable, whatever the weather.

 

R32 low GWP Refrigerant

Reducing environmental impact, airCore700 systems use R32 refrigerant which has a lower global warming potential (GWP) than traditional R410A refrigerant.

 

Frostwash Self-Cleaning Technology

All indoor units are equipped with FrostWash. FrostWash freezes the dirt and dust trapped in the indoor unit heat exchanger, which is drained away with the condensate when it defrosts – effectively cleaning the heat exchanger and helping to safeguard long-term performance by maintaining good airflow. FrostWash can be activated manually or automatically at scheduled intervals.

 

Human Sensor

The presence of occupants is detected through a motion sensor which divides the room into 4 zones – one for each louvre. For each of the 4 zones served by a cassette, air can be served either Direct or Indirect. Therefore one zone could receive direct airflow while another has indirect airflow, catering for different personal preferences of people occupying the same area.

Occupancy sensing technology

With CrowdSense technology, select units can determine how many people are in a space and adjust the cooling or heating capacity accordingly, so the room will never get too hot or cold, whether it’s crowded or almost empty.

No more cold feet

Visual elegance with Silent Iconic

A cassette panel that offers design integration as discreet as a more expensive ducted system. Designed to match the interior, in harmony with the space. Compared with the ceiling-duct-type, the installation cost can be reduced. Taking innovation a step further, the central inlet of the unit features louvres, ingeniously integrating it flawlessly into any ceiling.

 

In cooling scenarios, FloorSense Cool can prevent the floor area from overcooling by controlling airflow and cooling capacity so that the air at floor level does not get as cool as air above knee height.

Airflow control

Each louvre of the compact cassette can be individually controlled for comfortable airflow and adapted to any room configuration.

Advanced Wall Control

The SPX-WKT3 wall controller offers a fully-programmable 7-day timer so units can be switched on and off automatically to conserve power when rooms are unoccupied.

Other features include:

– Track power consumption
– Eco-mode
– Ventilation Speed
– Sleep mode
– Powerful mode
– Leave home function

Energy Efficient Comfort

RAI cassette air conditioners from Hitachi deliver low-energy heating by utilising high-efficiency inverter compressor technology.

When only a small amount of heating or cooling is required, it reduces energy input to save power.

HITACHI PCI-6.5UFA1NQ / PAS-6.5UFASMQ1 16.0kW R32 airCore700 4-WAY Cassette split system – 3 Phase – Brochure

Description

16.0 kW Cooling
18.0 kW Heating

R32 | Includes Wired Controller

air conditioning enquiry