MODEL | LGH-15RVX3-E | ||
25% (Default speed 1)
|
Air Volume
|
m3 /h | 38 |
l/s | 10 | ||
External Static Pressure | Pa | 8 | |
Temperature Exchange Efficiency
|
Heating % | 81.5 | |
Cooling % | 78 | ||
Enthalpy Exchange Efficiency
|
Heating % | 80.5 | |
Cooling % | 68 | ||
Specific Fan Power | W/(l/s) | 0.96 | |
Input Power | W | 10 | |
Sound Pressure Level | dB(A) | 17 | |
50% (Default speed 2)
|
Air Volume
|
m3 /h | 75 |
l/s | 21 | ||
External Static Pressure | Pa | 30 | |
Temperature Exchange Efficiency
|
Heating % | 78 | |
Cooling % | 73.5 | ||
Enthalpy Exchange Efficiency
|
Heating % | 76.5 | |
Cooling % | 61 | ||
Specific Fan Power | W/(l/s) | 0.72 | |
Input Power | W | 15 | |
Sound Pressure Level | dB(A) | 18 | |
75% (Default speed 3)
|
Air Volume
|
m3 /h | 113 |
l/s | 31 | ||
External Static Pressure | Pa | 68 | |
Temperature Exchange Efficiency
|
Heating % | 75.5 | |
Cooling % | 70.5 | ||
Enthalpy Exchange Efficiency
|
Heating % | 73.5 | |
Cooling % | 57 | ||
Specific Fan Power | W/(l/s) | 0.96 | |
Input Power | W | 30 | |
Sound Pressure Level | dB(A) | 22 | |
100% (Default speed 4)
|
Air Volume
|
m3 /h | 150 |
l/s | 42 | ||
External Static Pressure | Pa | 120 | |
Temperature Exchange Efficiency
|
Heating % | 73.5 | |
Cooling % | 65.5 | ||
Enthalpy Exchange Efficiency
|
Heating % | 70.5 | |
Cooling % | 52.5 | ||
Specific Fan Power | W/(l/s) | 1.32 | |
Input Power | W | 55 | |
Sound Pressure Level | dB(A) | 27 | |
DUCT SIZE | mm | 100 | |
WEIGHT | kg | 20 | |
DIMENSIONS WXDXH | mm | 780 x 610 x 289 | |
ELECTRICAL POWER SUPPLY | 220-240V, 50Hz | ||
Maximum Current | A | 0.57 | |
FUSE RATING (BS88) – HRC (A) | A | 6 | |
HEAT EXCHANGER | Paper with specially treated Cellulose Membrane | ||
STANDARD FILTER | ISO 16890 Coarse 60%* |
Mitsubishi Electric Lossnay Heat Recovery Ventilation LGH-15RVX3-E
Clean, fresh air | Energy efficient heat recovery
Includes a Lossnay Wired 7 Day Controller PZ-62DR-EB
Bypass Ventilation Mode
Stale room air is discharged to outside without passing through the Lossnay core. In spring and autumn when air conditioning is not necessary, the unit operates in bypass ventilation mode.
Heat recovery ventilation
Heat is recovered from the outgoing stale air. This heat is utilised to pre-heat incoming fresh air so your heating system is not required to work as hard to maintain desired room temperature.
Lossnay Ventilation Mode
Room air is discharged to outside via Lossnay core. Heat exchanged outside air is supplied to the room. In summer and winter, air conditioning energy can be recovered by Lossnay unit.
Filter (Supplied)
Filter cuts pollen and dust for fresh clean air. Replacement part no. P-220F-E. (G3 grade Classification :EN779:2012)
High Efficiency Supply Air filter (Optional)
The supply filter can be upgraded to the high efficency option, a non-washable high efficiency filter (M6 grade Classification :EN779:2012)
Night Purge (Requires PZ-61DR-E controller)
During the summer season, the Night Purge mode draws cooler outside air into the room at night. This energy conservation mode reduces the load when the air conditioning is started up the next morning. With new models, it is possible to manually engage and set the night purge operation.
Simultaneous air supply and exhaust
Lossnay is the ultimate home ventilation system that provides fresh clean air from outside, while removing both moisture and stale indoor air at the same time. Bringing in fresh air into the house can help improve air quality by lowering the amount of CO2.
- Air volume 42 l/s (model 15) to 556 l/s (model 200)
- Clean, fresh air
- Energy efficient heat recovery
- Simultaneous air supply and exhaust stale air
- Heat recovery ventilation
- Use with Mr Slim and City Multi systems
- Fresh air without windows open
- Retains heat
- Washable supply air filter
Description
42 l/s
Free Shipping Business Address Only