Mitsubihsi Electric Sensible Lossnay LGH-100RVS-E 278 l/s Heat Recovery Ventilation

SKU: LGH-100RVS-E / PZ-62DR-E

Includes a Lossnay Wired Controller PZ-62DR-E



 

Unit: mm

LGH-100RVS-E

Weight

73kg (89kg with maximum drain water)

Electrical Power Supply

220 – 240V/50Hz, 220V/60Hz

Fan Speed

Input Power

W

100%

75%

50%

25%

Test condition

445

225

100

35

ISO 16494

Temperature exchange efficiency is winter condition

Airflow

m3/h

1000

750

500

250

L/S

278

208

139

69

Specific Fan Power

W/(L/S)

1.60

1.08

0.72

0.50

External Static Pressure

Pa

190

107

48

12

Temperature Exchange Efficiency %

82.0

84.0

86.0

90.0

Noise

dB

37.0

32.0

24.0

18.0

A-weighted sound pressure level @1.5m off from the center of the unit in an anechoic chamber

Exhaust Air Transfer Ratio %

Insulation Resistance

5

Tracer gas method @100% airflow (prEN308)

10MΩ or more

Dielectric Strength

Maximum Current

A

AC 1000V 1 minute

4.20

Inrush Current

A

6.1A @10ms, 3.6A @100ms

  • Fresh air ventilation with energy-efficient heat recovery
  • Perfect for higher humidity environments
  • Plug and play CO2
  • sensor control including power
  • Digital commissioning of fan speed increments
  • Easy control interlock with Mr Slim and
  • City Multi air conditioning systems
  • M-NET connection for centralised control
  • Integrated bypass damper for free cooling
  • In-built condensate drainage traps

Mitsubihsi Electric Sensible Lossnay LGH-100RVS-E 278 l/s Heat Recovery Ventilation – Brochure

Description

278 l/s – Sensible Lossnay
Free Shipping Business Address Only

air conditioning enquiry